INDUSTRIAL VENTILATION · ATEX GUIDE
Does your installation involve an explosive atmosphere?
Flammable gases, vapours or dust: start with the zoning defined for your site. It guides the equipment and marking to be considered.
Understand the essentialsVisual guide
From risk to the right marking
Follow the path: atmosphere, site zone, equipment category, then marking.
Where and when can it occur?
Choose a medium to see its zone scale.
The zone describes the location. It comes from the installation zoning document.
Which category should you check?
Category = equipment · G = gas · D = dust
Important Product sheets below cover Categories 2 and 3. Zones 0 / 20 require Category 1.
Decode a marking
Select a token to understand its role.
II: equipment intended for surface industries.
LEARNING EXAMPLE · INCOMPLETE FRAGMENTMotor guide
Which motor marking for each zone?
Start with the zone listed in your site documentation, then check the complete motor nameplate and the conditions in its instructions.
Very high protection is required. A marking limited to Ex db, Ex eb or Ex ec is not sufficient for this zone.
Ex db: flameproof enclosure. Ex eb: increased safety. These protection types can correspond to EPL Gb when the certificate covers the motor and its use.
Ex ec: increased safety for EPL Gc. An EPL Gb motor may also be assessed for Zone 2 when the other parameters match.
Ex db IIC T4 Gb — learning example
Select each element: a real nameplate may include other codes and conditions.
Ex: equipment designed according to one or more explosion protection types.
The markings after the protection code matter too. Check gas or dust group, T / °C, Ta or Tamb (ambient), IP, voltage, frequency, speed and inverter use. Certificate suffix X signals specific conditions; U identifies a component rather than complete equipment. Case matters: db is a gas protection type, while Db is a dust EPL. A motor alone does not certify the assembled fan.
Ex eb, Ex db or Ex ec alone is never enough to select a motor: the complete nameplate, certificate, instructions, gas or dust, ambient temperature and fan assembly must match the application. Have the selection confirmed before ordering.
These visuals provide general guidance: site zoning comes from the risk assessment, and each item’s complete marking must be checked for the application. Prevention guidance (INRS) ↗
Selection assistant
From site zone to fan + motor marking
Answer five steps. The result separates the target marking for the fan and its motor.
- 01Atmosphere
- 02Zone
- 03Substance
- 04Motor
- 05Result
1. Which atmosphere is listed in the zoning document?
Use the zoning document prepared for the installation.
2. Which zones are specified?
For a mixed atmosphere, select one zone for each type.
3. What are the substance characteristics?
Use the risk assessment or safety documentation; do not estimate these values.
4. Where is the motor, and which protection type is specified?
If the motor is in another zone, specify it. Select the project protection type or check its documentation.
5. Marking profile to specify
The result distinguishes the fan from the motor.
Target profile to confirm, not certification of an AIRAP model. Actual marking depends on the selected model certificate, instructions, assembly and operating conditions.
Zoning comes from the installation risk assessment. In mixed atmospheres, gas and dust requirements remain separate. A calculated profile does not replace checking the complete assembly certificate.
Understand ATEX zoning and markings ↗Product sheets
Fans listed in the ATEX catalogue
Open a product sheet to review the characteristics and documents for that reference.
HC
Select a product sheet to view its reference details.
HC
Ventilador axial para instalação em conduta, virola curta HCC ou longa HCL com flanges de ligação, acoplamento direto.
Ver produto
HC · com bocal
virola abocinada curta HCCP ou longa HCLP com flanges de ligação, acoplamento direto.
Ver produto
HC 400°C/2H
extração de fumos · Ventilação de edifícios de serviços virola curta HCC ou longa HCL com flanges de ligação, acoplamento direto : F400 120 Diâmetro do impulsor / hélice : 400– 1600mm Caudal : 0–…
Ver produtoV-SOD
Select a product sheet to view its reference details.
V SOD
Ventilador centrífugo de aspiração simples, impulsor de ação, pás estampadas TUE, acionamento direto, voluta soldada por pontos, em aço galvanizado, aço inoxidável, alumínio.
Ver produtoVP-SOD
Select a product sheet to view its reference details.
VP SOD
Ventilador centrífugo de aspiração simples, equipado com impulsor TURA de ação de elevada eficiência com pás montadas, acionamento direto, voluta soldada por pontos, em aço galvanizado, aço inoxidável, alumínio.
Ver produtoRoof fans
Select a product sheet to view its reference details.
JET
Atmosferas explosivas · Ventilação industrial · Ventilação de edifícios de serviços Extrator centrífugo de cobertura, em polipropileno, descarga vertical Diâmetro do impulsor / hélice : 200– 300mm…
Ver produto
TE-V
Extrator centrífugo de cobertura, em aço galvanizado, aço inoxidável … Extração pela cobertura.
Ver produto
TE-VP
Extrator centrífugo de cobertura, em aço galvanizado, aço inoxidável … Extração pela cobertura.
Ver produto